Taskforce Logo
General6 views0% helpful (0 votes)

Voltage Polarity Compliance

Extract from AS/NZS3019:2001

Jason Bright

Updated 18 February 2026
Extract from AS/NZS3019:2001
(c) Conductors of cables are correctly identified and are connected to the correct terminals of fittings;
(j) Exposed metal liable to become alive is connected to earth.
Polarity testing shall be performed to the extent that it is reasonably practical, with any significant omission being reported. Testing is intended to confirm the following:
(a) Every single-pole switch or protective device of the electrical installation operates in the active conductor of the circuit in which it is connected; and
(b) Every RCD operates in the active conductor of the circuit(s) to which it is connected, and in the neutral conductor as specified in AS/NZS 3000.

Was this article helpful?

Related Articles

General

Dishwasher Problems

A dishwasher that doesn’t clean dishes is hardly a dishwasher at all. Make sure that your dishwasher isn’t dirty, to begin with, checking the strain screen, sprayer arms, and door gasket for food part

630

Still Need Help?

Can't find the answer you're looking for? Our support team is here to help.