Wiring rules 2.10.5

Jason Bright

Updated 18 August 2026
Wiring rules 2.10.5
Wiring rules 2.10.5.6
Where the making of the fuse base does not correctly indicate the rating of the associated fuse-element, the rating of the fuse-element shall be marked either on an exposed non-detachable portion of the fuse or on its enclosing case, or on the switchboard adjacent to the fuse.