Electrical Polarity

AS/NZS 3019:2007 Voltage Polarity Compliance

Jason Bright

Updated 18 February 2026
AS/NZS 3019:2007 Voltage Polarity Compliance
(c) Conductors of cables are correctly identified and are connected to the correct terminals of fittings;
(j) Exposed metal liable to become alive is connected to earth.
Polarity testing shall be performed to the extent that it is reasonably practical, with any significant omission being reported. Testing is intended to confirm the following:
(a) Every single-pole switch or protective device of the electrical installation operates in the active conductor of the circuit in which it is connected; and
(b) Every RCD operates in the active conductor of the circuit(s) to which it is connected, and in the neutral conductor as specified in AS/NZS 3000.

Was this article helpful?

Related Articles

Electrical Safety

What is included in an Electrical safety check?

Changes to the Residential Tenancies Act 1997 (Vic) increased the mandatory safety obligations on electrical safety checks from 29 March 2021. Every two years, an electrical safety check must be carri

120
Electrical Safety

What is included in an Electrical safety check?

Changes to the Residential Tenancies Act 1997 (Vic) increased the mandatory safety obligations on electrical safety checks from 29 March 2021. Every two years, an electrical safety check must be carri

100
Electrical Safety

Electrical Obstructions

Obstructions present in an electrical testing job can mean that our electricians cannot safely and accurately complete their job. Some obstructions can be a health and safety hazard, such as dirty kit

100

Still Need Help?

Can't find the answer you're looking for? Our support team is here to help.